| Model Number |
25 |
33 |
40 |
48 |
60 |
80 |
100 |
120 |
150 |
| Performance Data |
Nominal cooling capacity |
Btu/h |
26000 |
28-33400 |
35-40500 |
44-48600 |
52-62000 |
72-80400 |
85-107000 |
125000 |
157000 |
| Nominal air flow rate |
cfm |
800 |
1200 |
1400 |
1600 |
2000 |
2600 |
3200 |
4000 |
4800 |
| Electrical Data |
Power supply |
V / Ph / Hz |
220/1/50 |
| Pre-filter / Air filter |
Type |
Plastic |
| Coil Data |
Fin type |
Type |
Corrugated |
| Blower |
Type |
Type |
Single inlet |
| Number used |
n |
1 |
2 |
| Blower motor |
Motor |
Type |
Permanent Split Capacitor |
| Drive |
Type |
Direct |
| No. of motors |
n |
1 |
2 |
| Liquid line size |
in |
3/8 |
1/2 |
5/8 |
| Piping |
Gas line size |
in |
5/8 |
3/4 |
1 1/8 |
1 3/8 |
1 5/8 |
| Connections |
Drain connection size |
in |
1 |
| Dimensions |
Height (Box / Unit) |
mm |
1655/1615 |
1910/1870 |
| Length (Box / Unit) |
mm |
650/600 |
895/846 |
1135/1090 |
1631/1586 |
| Depth(Box / Unit) |
mm |
365/320 |
465/420 |
| Weight Approx |
Net / Shipping |
kg |
50 |
58 |
68 |
72 |
88 |
96 |
139 |
145 |
165 |
|